Tabl e 4- 1Error Codes for Troubleshooting the MJI-1500-01
Error Code
Description
Displayed
of Error
System Over
Temperature
Shutdown
DC input
Under Voltage
Warning
AC Output
Overload
Warning
System Over
Temperature
Warning
Car lighter
port #1 fused
4-3
Description of Condition
Unit shuts down.
System internal temperature is above
operation limit.
The alarm will continue to beep once
every second.
Backlight changes from pink color
flashing to red color flashing. After the
alarm continues for 1 minute, the
backlight and alarm will turn off. Only
the error code will be shown
continuously.
System is still operating but input
voltage has dropped too close to the
shutdown limit (11.0 to 10.7 VDC).
Backlight appears to be pink
color flashing
System is still operating but AC load
applied to the system in inverter mode
is close to shutdown limit.
Backlight appears to be pink
color flashing
System is still operating but system
internal temperature is close to
shutdown limit.
Backlight appears to be pink
color flashing
DC lighter plug output current is more
than 15A,
Backlight appears to be pink
color flashing, and alarm continues
until the fuse is replaced.
Troubleshooting
Resolution
Remove excess AC loads.
Reset of unit is required.
To reset the unit, turn it OFF
and back ON
Check the system ventilation
and reduce the load applied
to the system.
Unit continues to run.
If the warning is ignored, the
unit will eventually goes to the
E01 fault condition.
Unit continues to run.
If the warning is ignored, the
unit will eventually go to the
E03 fault condition.
Unit continues to run.
If the warning is ignored, unit
will eventually go to the E04
fault condition.
Replace fuse.
Reduce the load to DC
lighter plug
Remove the output
short-circuit.