Ingeteam
Alarm
Lighting*
Grid consumption
Orange, 1
Low pow. PV conn.
Orange, 1
Pow. supply fault
Not applicable Not applicable
Idc grid injection
Not applicable Not applicable
Config. change
Isolation alarm
Orange, 5
Satur. alarm Iac
Orange, 5
Low Vdc
Orange, 1
Shut-off due to
Not applicable Not applicable
burn-out
Electric arc detection
Orange, 8
* The number of flashes is indicated.
Warnings
Alarm
Lighting*
Blocked fan
Orange, 7
High temperature
Orange, 7
Low temperature
Orange, 7
High Vdc
Not applicable Not applicable
String kit comm.
Not applicable Not applicable
Self-cons. commun.
Orange, 7
Surge arrester error
Not applicable Not applicable
* The number of flashes is indicated.
88
LED
Description
Grid consumption power out of the
permitted range
The generated power in the PV
array is not sufficient to connect to
the AC grid
Red, 1
Inverter setting change
Insulation resistance out of range
AC current saturation
Low DC voltage
Electric arc detected in the DC
input
LED
Description
Possible fan blockage
Power regulation due to
temperature above operating
temperature
Temperature below operating
temperature
Communication fault with the self-
consumption devices (wattmeter
or INGECON EMS Manager)
Solution
This may be due to a low irradiance level. Otherwise,
check the PV array.
Not applicable
Not applicable
Normal shut down due to a change in the inverter
setting.
Check, on the display, that the PV array grounding is
correctly configured. Search for an insulation fault in
the PV array. If one of the poles is grounded, check
the grounding fuse.
Check the installation in the AC part.
If the error persists, contact the Technical Service.
This may be due to a low irradiance level. Otherwise,
check the PV array.
Not applicable
Not applicable
Solution
Check the condition of the fan and that there are no
elements that prevent it functioning properly.
Check the room temperature does not exceed the
specified maximum temperature and the inverter
is not exposed to direct sunlight. Also check the
functioning of the fans.
Check the room temperature is not below the
specified minimum temperature.
Not applicable
Not applicable
Check the connection of the different elements. If
the error persists, contact the Technical Service.
Not applicable
ABE2011IQM01_B - Installation and Operation Manual
Troubleshooting