Scrolling Time

Selección de la duración de la visualización de los datos del menú del usuario,
antes de volver a la página predeterminada.
3 segundos
3 s
5 segundos (
s s
10 segundos
10 s
30 segundos
30 s
1 minuto
1 MiN
5 minutos
5 MiN
10 minutos
10MiN
Manual scroll
MAn.Sc .
128
Display Special Functions

Special functions disabled
diSAb.
Shows the setpoint on display 1 and the process on
SWAP
display 2 (only if Par. 123
129
NFC Lock

Disables NFC capabilities
NFC lock Disabled: behaviour, the device can be programmed via
diSAb.
NFC using the PROGRAMADOR smartphone app. (
NFC lock Enabled: NFC protection active, the device will ignore
EnAb.
any configuration update written through nfc.
130
Set key special functions

Assign special functions to the
No special function linked to the
diSAb.
Start/Stop. Pressing
st . /st .
versa. Status of the controller, upon power-up, depends on parameter 30
2 Threshold Switch. The controller changes the regulation
2t .swi .
setpoint alternating between Set1 and Set2
3 Threshold Switch. The controller changes the regulation
3t .swi .
setpoint alternating between Set1, Set2 and Set3
4 Threshold Switch. The controller changes the regulation
4t .swi .
setpoint alternating between Set1, Set2, Set3 and Set4
Analogue Input 0. Set the analog input to zero (zero tare)
A. i . 0
131÷140
Reserved Parameters - Group I
Reserved parameters - Group I.
11.j
GROUP J -

141
Loop Break State
 
Loop break disabled. (
diSAb.
Loop break enabled with automatically calculated time and band.
autom.
Loop break enabled with time (par.
manu.
142
Loop Break Time
 
Sets the maximum time span allowed for a process variation to occur before the loop break error is
triggered. The minimum delta variation considered is set in P_143 (
00:01..99:59 mm:ss.
143
Loop Break Band
 
Sets the minimum delta process variation required to occur (within the timeframe set in P_142
in order to avoid a loop break error
1..+10000 [digit
1 p. 37
144÷148
Reserved Parameters - Group J
Reserved parameters - Group J.
11.k
GROUP K -

149
Modbus Slave

Disabled
diSAb.
Enabled. (
EnAb.
)
Por defecto
set on

button. To execute the function the key must be pressed for 1 s.
SET
key the controller switches from Start to Stop and vice
SET
- Loop Break
)
Default
: 02:00 mm:ss.
Default
] (degrees.tenths for temperature sensors).
- Serial communication Slave
)
Default
)
  
Default
key. (
)
SET
Default
) And band (par.
 
(available on xxxx-T)
)

) entered by the user.
 
)
 
10.0°C.
Default
)
 
33