,127
Scrolling Time
Selección de la duración de la visualización de los datos del menú del usuario,
antes de volver a la página predeterminada.
3 segundos
3 s
5 segundos (
s s
10 segundos
10 s
30 segundos
30 s
1 minuto
1 MiN
5 minutos
5 MiN
10 minutos
10MiN
Manual scroll
MAn.Sc .
128
Display Special Functions
Special functions disabled
diSAb.
Shows the setpoint on display 1 and the process on
SWAP
display 2 (only if Par. 123
129
NFC Lock
Disables NFC capabilities
NFC lock Disabled: behaviour, the device can be programmed via
diSAb.
NFC using the PROGRAMADOR smartphone app. (
NFC lock Enabled: NFC protection active, the device will ignore
EnAb.
any configuration update written through nfc.
130
Set key special functions
Assign special functions to the
No special function linked to the
diSAb.
Start/Stop. Pressing
st . /st .
versa. Status of the controller, upon power-up, depends on parameter 30
2 Threshold Switch. The controller changes the regulation
2t .swi .
setpoint alternating between Set1 and Set2
3 Threshold Switch. The controller changes the regulation
3t .swi .
setpoint alternating between Set1, Set2 and Set3
4 Threshold Switch. The controller changes the regulation
4t .swi .
setpoint alternating between Set1, Set2, Set3 and Set4
Analogue Input 0. Set the analog input to zero (zero tare)
A. i . 0
131÷140
Reserved Parameters - Group I
Reserved parameters - Group I.
11.j
GROUP J -
141
Loop Break State
Loop break disabled. (
diSAb.
Loop break enabled with automatically calculated time and band.
autom.
Loop break enabled with time (par.
manu.
142
Loop Break Time
Sets the maximum time span allowed for a process variation to occur before the loop break error is
triggered. The minimum delta variation considered is set in P_143 (
00:01..99:59 mm:ss.
143
Loop Break Band
Sets the minimum delta process variation required to occur (within the timeframe set in P_142
in order to avoid a loop break error
1..+10000 [digit
1 p. 37
144÷148
Reserved Parameters - Group J
Reserved parameters - Group J.
11.k
GROUP K -
149
Modbus Slave
Disabled
diSAb.
Enabled. (
EnAb.
)
Por defecto
set on
button. To execute the function the key must be pressed for 1 s.
SET
key the controller switches from Start to Stop and vice
SET
- Loop Break
)
Default
: 02:00 mm:ss.
Default
] (degrees.tenths for temperature sensors).
- Serial communication Slave
)
Default
)
Default
key. (
)
SET
Default
) And band (par.
(available on xxxx-T)
)
) entered by the user.
)
10.0°C.
Default
)
33