Closed Loop Vector Mode - Control Techniques UNIDRIVE SP1201 Guía Rápida

Ocultar thumbs Ver también para UNIDRIVE SP1201:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Safety
Product
Mechanical
Information
Information
Installation
7.2.2

Closed loop vector mode

Induction motor with incremental encoder feedback
For simplicity only an incremental quadrature encoder will be considered here. For
information on setting up one of the other supported speed feedback devices, refer to
Setting up a feedback device in the Unidrive SP User Guide on the CD Rom supplied
with the drive.
Action
Ensure:
Before
Drive Enable signal is not given (terminal 31)
power-up
Run signal is not given
Motor and feedback device is connected
Ensure:
Power-up
Drive displays 'inh'
the drive
If the drive trips, see
Incremental encoder basic set-up
Enter:
Drive encoder type in Pr 3.38 = Ab (0): Quadrature encoder
Encoder power supply in Pr. 3.36 = 5V (0), 8V (1) or 15V (2)
Set motor
feedback
CAUTION
parameters
Drive encoder Lines Per Revolution (LPR) in Pr 3.34 (set
according to encoder)
Drive encoder termination resistor setting in Pr. 3.39:
Enter:
Motor rated frequency in Pr 0.47 (Hz)
Enter motor
Motor rated current in Pr 0.46 (A)
nameplate
Motor rated speed (base speed - slip speed) in Pr 0.45 (rpm)
details
Motor rated voltage in Pr 0.44 (V) - check if
Set
Enter:
maximum
Maximum speed in Pr 0.02 (rpm)
speed
Set
Enter:
acceleration
Acceleration rate in Pr 0.03 (s/1000rpm)
/
Deceleration rate in Pr 0.04 (s/1000rpm) (If braking resistor fitted,
deceleration
set Pr 0.15 = FAST. Also ensure Pr 10.30 and Pr 10.31 are set
rates
correctly, otherwise premature 'It.br' trips may be seen.)
34
Electrical
Getting
Installation
Started
Chapter 9 Diagnostics
Setting the encoder voltage supply too high for the
encoder could result in damage to the feedback device.
0 = A-A\, B-B\, Z-Z\ termination resistors disabled
1 = A-A\, B-B\, termination resistors enabled, Z-Z\ termination
resistors disabled
2 = A-A\, B-B\, Z-Z\ termination resistors enabled
www.controltechniques.com
Running
Advanced
Menu 0
the motor
parameters
Detail
on page 39.
or
connection
Unidrive SP Short Form Guide
UL Listing
Diagnostics Appendix
Information
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55
I.cl F
°
C 40 s S1
-1
V
Hz min
kW
cosφ
230
50 1445 2.20 0.80 8.50
400
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
1000rpm
0.03
Issue Number: 1
A
4.90
4.90
t
t
0.04

Publicidad

Tabla de contenido
loading