Safety
Product
Mechanical
Information
Information
Installation
Trip
HF27
Power stage thermistor 1 fault
227
Hardware fault - return drive to supplier
HF28
Power stage thermistor 2 fault or internal fan fault (size 3 only)
228
Hardware fault - return drive to supplier
HF29
Control board thermistor fault
229
Hardware fault - return drive to supplier
HF30
DCCT wire break trip from power module
230
Hardware fault - return drive to supplier
HF31
Aux fan failure from power module
231
Replace auxiliary fan
HF32
Power stage - a module has not powered up in a multi-module parallel drive
232
Check AC power supply
It.AC
Output current overload timed out (I
Ensure the load is not jammed / sticking
20
Check the load on the motor has not changed
Tune the rated speed parameter (closed loop vector only)
Check feedback device signal for noise
Check the feedback device mechanical coupling
It.br
Braking resistor overload timed out (I
Ensure the values entered in Pr 10.30 and Pr 10.31 are correct
19
Increase the power rating of the braking resistor and change Pr 10.30 and Pr 10.31
If an external thermal protection device is being used and the braking resistor software overload is
not required, set Pr
O.CtL
Drive control board over temperature
Check cubicle / drive fans are still functioning correctly
23
Check cubicle ventilation paths
Check cubicle door filters
Check ambient temperature
Reduce drive switching frequency
O.ht1
Power device over temperature based on thermal model
Reduce drive switching frequency
21
Reduce duty cycle
Decrease acceleration / deceleration rates
Reduce motor load
O.ht2
Heatsink over temperature
Check cubicle / drive fans are still functioning correctly
22
Check cubicle ventilation paths
Check cubicle door filters
Increase ventilation
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
Oht2.P
Power module heatsink over temperature
Check cubicle / drive fans are still functioning correctly
Check cubicle ventilation paths
Check cubicle door filters
Increase ventilation
105
Decrease acceleration / deceleration rates
Reduce drive switching frequency
Reduce duty cycle
Reduce motor load
Unidrive SP Short Form Guide
Issue Number: 1
Electrical
Getting
Menu 0
Installation
Started
2
t) - accumulator value can be seen in Pr 4.19
2
t) – accumulator value can be seen in Pr 10.39
10.30
10.31
or Pr
to 0 to disable the trip
www.controltechniques.com
Running
Advanced
Diagnostics
the motor
parameters
Diagnosis
UL Listing
Appendix
Information
43