Benning DUSPOL expert Manuel De Instrucciones página 9

Ocultar thumbs Ver también para DUSPOL expert:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 14
(the phase indication only works in an earthed AC voltage
mains) and the vibration motor (the vibration motor is activated
by actuating both push-buttons). The installation is only free
of voltage, if all three test circuits (voltage indication, phase
indication and vibration motor) are signaling the absence of
voltage.
-
Apply the two probe tips L1/+
parts to be tested.
-
The level of voltage applied is indicated by means of the
LED step indicator 
A flashing LED step indicates that the voltage value of this 
LED  step  has  not  been  reached  (except  for  LED  12  V/ 
24 V). A LED step will start to light from 75 % to 85 % of 
the step value onwards.
 Alternating voltages (AC) are indicated by the + 12 V LED 
and the - 12 V LED lighting up simultaneously.
Direct  voltages  (DC)  are  indicated  by  the  +  12  V  LED 
or  the  -  12  V  LED  lighting  up. The  polarity  indication 
shows the polarity (+ or -) applied to the probe tip L2/+
-
To differentiate between low-energy and high-energy volt-
ages (e.g. capacitively induced interference voltages), an
internal load in the voltage tester can be connected by ac-
tuating both push-buttons (see section 5).
Overload indication
If the voltage applied to the probe tips L1/-
is  higher  than  the  admissible  nominal  voltage,  all  LEDs  of 
the step indicator
1,100 V AC/DC on.
5.
Load connection with vibration motor (figure B/C)
Both handles L1
6
. Here, voltage is applied to a vibration motor (motor with
unbalanced mass) in the display handle L2
From  approx.  200  V  on,  this  motor  is  set  in  rotary  motion. 
With the voltage increasing, the motor's speed and vibration
increases as well. The duration of the test with a lower inter-
nal resistance (load test) depends on the level of voltage to
be measured. In order to avoid an inadmissible warming of
the device, it is provided with a thermal protection (controlled
reduction). With this controlled reduction, the speed of the vi-
bration motor is reduced and the internal resistance increases.
The load connection (with both push-buttons being actuated)
can be used ...
-
to suppress reactive voltages (inductive and capacitive
voltages),
-
to charge capacitors,
-   to trip 10/30 mA RCD safety switches. The tripping of the 
RCD safety switch is done by testing the external conduc-
tor (phase indication) to PE (earth). (figure D)
6.
External conductor test (phase indication) (figure D)
-
Fully grasp the handles L1
sure a capacitive coupling to earth.
-
Apply the probe tip L2/+
During the single-pole external conductor test (phase in-
dication), make absolutely sure not to touch the probe tip
2
L1/-
If the red LED 
conductor (phase) of an AC voltage is applied to this sys-
tem part.
Note:
The single-pole external conductor test (phase indication)
can be carried out in an earthed mains from 230 V, 50/60 Hz 
(phase to earth) on. Protective clothing and insulating condi-
tions on site might impair the function.
Attention!
The absence of voltage can only be determined by means of
a two-pole test.
7.
Phase sequence test (figure F/G)
-
Fully grasp both handles L1
sure a capacitive coupling to earth.
-
Apply the probe tips L1/-
conductors (phases) and check whether the external con-
ductor voltage of e.g. 400 V is applied.
-
A clockwise phase sequence (phase L1 before phase L2)
is given, if the green LED ► of the phase sequence indica-
tion
L
-
A counter-clockwise phase sequence (phase L2 before
phase L1) is given, if the green LED ◄ of the phase se-
quence indication
-
The phase sequence test always requires a countercheck
with the probe tips L1/-
ing which the phase sequence must change.
Note:
The phase sequence test can be carried out in an earthed
three-phase mains from 400  V  -  900  V,  50/60  Hz  (phase  to 
phase) on. Protective clothing and insulating conditions on site
might impair the function.
8.
Continuity test (figure H)
-
The continuity test must be carried out on system parts
which are free of voltage. If necessary, capacitors have to
be discharged.
-
Apply the two probe tips L1/-
parts to be tested.
-   In  case  of  continuity  (R  <  100  kΩ),  an  acoustic  signal  is 
emitted and the yellow LED Ω 
-
This function also can be used to determine the conducting
and non-conducting direction of semiconductor components.
-
If a voltage is applied to the test point, the voltage tester
automatically switches over to the voltage test function
and indicates this function.
9.
Cable break detector (figure I)
-
The cable break detector is intended for the non-contact
localization of cable breaks on exposed live lines.
02/ 2019
9
9
 are flashing. Overload is indicated from 
7
and L2
and that it remains contactless.
 K
lights up.
L
DUSPOL
2
and L2/-
.
8
are equipped with push-buttons
7
and L2
3
to the system part to be tested.
lights up on the display, the external
7
and L2
2
and L2/+
lights up.
2
and L2/+
2
and L2/+
M
expert
®
3
to the system
2
and L2/+
8
.
8
, in order to en-
8
, in order to en-
3
to two external
3
being inverted dur-
3
to the system
for continuity lights up.
J
3
.
3
6

Publicidad

Tabla de contenido
loading

Tabla de contenido