Priming Setup Example
The following example illustrates the steps to set up Priming Mode. The control panel buttons are pictured
below to help you become familiar with their appearance and function.
To set up the Priming Mode fl ow rate and time:
1. Be sure that the green power LED is on and the pump is stopped. If the
pump is running, press the
2. Press the
3. Press the
4. Press the
Priming Flow" is displayed. Press the
5. To change the Max Priming Flow setting, press the
arrows to select which digit to modify.
•
Press the
6. When the desired value is displayed, press the
the changes.
•
Press the
7. Use the
Up and Down arrows to scroll to "Max Priming Time" or
"System Priming Time." Press the
8. To change the Max Priming Time setting, press the
arrows to select which digit to modify.
•
Press the
9. When the desired value is displayed, press the
the changes.
•
Press the
IntelliFlo VF Installation and User's Guide
Start/Stop button to stop it.
Menu button. "Pool Data" is displayed.
Down arrow to scroll to the "Priming" menu item.
Select button to select the "Priming" menu item. "Max
Up and Down arrows to change the selected digit.
Escape button to exit edit mode without saving.
Up and Down arrows to change the selected digit.
Escape button to exit edit mode without saving.
Select button to select it.
Left and Right
Enter button to save
Select button to select it.
Left and Right
Enter button to save
Priming Setup
MENU
14:09
Pool Data
MENU
14:09
Priming
Priming
14:09
13 m³/h
Max Priming Flow
Priming
14:09
0013
m³/h
Max Priming Flow
Priming
14:09
0013
m³/h
Max Priming Flow
Priming
14:09
0023
m³/h
Max Priming Flow
Priming
14:09
0023
m³/h
Max Priming Flow
Priming
14:09
0020
m³/h
3X
Max Priming Flow
Priming
14:09
20
m³/h
Max Priming Flow
Priming
14:09
15. MIN
Max Priming Time
Priming
14:09
0. MIN
S y s t e m P r i m i n g T i m e
MENU
14:09
Priming