KDP-DALI 01
Presence detector for DALi lighting control

Function

Auto mode
Under auto mode, the load will turn on automatically when the
movement is detected and the ambient light level is below the Lux
setting value. When no movement is detected and the delay time
has expired, the load will turn off or switch to standby mode
automatically.
According to the changeable ambient light level, detector can
postpone delay time of turning on and off of load(light) to avoid
unnecessarily switching on or off due to rapid ambient light change:
Ambient light level changes from bright to dark:
level keeps to be lower than the pre-set Lux value for 10sec, the light
will be automatically switched on after 10sec. (LED will be on 10sec for
indication)
Ambient light level changes from dark to bright:
light level continuously exceeds the switch off Lux value for 5min,
there are different reactions according to the time setting value.
Time setting 5min, the light will be automatically switched off after
5min.
Time setting < 5min, the light will be automatically switched off when
the set time reached if no movement is detected during the 5min. But
if there is movement detected within the 5min, the time will be reset
upon detection and until 5min later, the light is switched off.
Standby mode function
Set "STBY" knob to "∞" under auto mode, detector will enter into
2-level mode when the delay off time is expired, and load will change
to turn on according to the setting of "STBY%" . During which, if the
movement is detected, load will turn on with the setting illumination
(100% or the dimmed illumination) and then turn to the setting
illumination of "STBY%" if no movement detected and the delay off
time expired. It will be cycled until the ambient light level is higher
than the switch off Lux value and lasts for 5min, then turns off and
detector enters into standby mode. During which, if the ambient light
level is below the pre-set Lux value again, detector will enter into
2-level mode automatically.