Operation and function
Time, Lux, STBY and STBY% knobs
Knob
Time
10m.
5m.
30m.
1m.
60m.
Test
Lux
100
300
5
2000
STBY
10m
15m
∞
5m
STBY%
10%
20%
OFF
30%
Lux learning function with knob
Learning procedure:
•
Adjust the knob to "
desired value (See FIG.10-A).
•
When the knob is set to "
position more than 1sec, then goes back to "
•
Then the load is off. red LED starts to flash slowly indicating entering into
learning mode. Learning will be completed within 25 seconds. Afterwards,
the red LED and load will keep on 5sec or red LED flashes quickly for 5sec
and load is off to confirm successful learning (See FIG.10-C).
•
After learning procedure, the detector returns to AUTO mode with red
LED and load being off.
www.grupotemper.com
Function
Set delay off time for
load lighting
Set the light value for
switching on load
lighting
Set load on time in
standby mode
Set load illumination
in standby mode
" when the ambient light level matches with the
" originally, it should be adjusted to other
Presence detector for DALi lighting control
Knob setting
Range : Approx. 1min to 60min
Test
: Test mode (Load and red
LED will be 2sec on, 2sec
off)
Range
:Adjustable from
approx.5 to 2000Lux.
(learn): The actual ambient
light level
(10 - 2000Lux) can be
read in.
3 precise adjustments: 5min,
10min, 15min, plus ∞.
3 precise adjustments: 10%, 20%,
30% and OFF (Load is off in
standby mode)
" (See FIG.10-B).
KDP-DALI 01
Instructions manual |
37