KDP-DALI 01
Presence detector for DALi lighting control
Walk test (Lux setting is inactive)
The purpose of conducting walk test is to check and adjust detection
coverage. Set Time knob to "Test", then conducting a walk test.
It takes approx. 60sec for detector to warm up after power is supplied,
then detector enters into normal operation to carry out a walk test.
Test procedure
1.
Tester must be within the detection coverage.
2.
Switch power on.
3.
It takes approx. 60sec for detector to warm up with load and red LED on,
then turns off after warming up time.
4.
Walk from outside across to the detection pattern until red LED turns on
for approx. 2sec then off, the next trigger should be 2sec interval
(See FIG.13).
5.
Adjust lens shield for desired detection range.
6.
Repeat step 4 and 5 until it meets user's demands.
Instructions manual |
FIG.12
NOTE
FIG.13
40