Usage of lens shield

KDP-DALI 01 / KDP-DALI 01-C has provided 2 lens shields for masking the
undesired detection area. Each lens shield has 3 layers (Layer A / Layer B /
Layer C), each layer includes 6 small segments and each small segment can
cover 30° detection angle. For example, install the detector at the height of
2.5m, the detection range can reach up to 1m diameter if the two complete
lens shields have been used, and up to 4m diameter if the A & B layers of
two lens shield has been used, and up to 6m diameter if only the A layer of
two lens shield has been used, and up to 7m diameter if no lens shield
has been used.
The whole lens shield is used.
A
B
C
A layer of the lens shield is used.
• The shadow part of the lens shields in the FIG.11 is referring to
the cut off parts.
After user choosing the desired detection area, the redundant lens shield
should be eliminated.
Fixing lens shield: There is circular hook on the back of the decorative frame
and the lens shield is designed with a circular groove. The lens shield can be
fitted by joining the groove of lens shield with its corresponding hook on
the decorative frame (See FIG.12).circular. O protetor de lente pode ser
encaixado ao juntar o sulco do protetor de lente com o gancho
correspondente na moldura decorativa (Ver FIG. 12).
www.grupotemper.com
Presence detector for DALi lighting control
A & B layer of the lens shield is used.
Φ1m
Part of the lens shield is used.
Φ6m
FIG.11
KDP-DALI 01
Φ4m
Φ1m
Φ4m
o
30
Φ6m
Φ7m