Electrical Installation; Supply Voltage - Grundfos Intertek MAGNA1 Installation And Operating Instructions

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Electrical installation

Carry out the electrical connection and protection according to
local regulations.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
Warning
Switch off the power supply before making
connections.
Warning
Never make any connections in the pump control
box unless the power supply has been switched
off for at least 5 minutes.
Warning
The pump must be connected to an external
mains switch with a contact separation of at least
1/8 inch (3 mm) in each pole.
The ground terminal of the pump must be earth
ground.
Grounding or neutralization can be used for
protection against indirect contact.
If the pump is connected to an electric
installation where a Ground Fault Circuit
Interrupter (GFCI) is used as additional
protection, this circuit interrupter must trip out
when ground fault currents with DC content
(pulsating DC) occur.
If rigid conduit is to be used, the hub must be connected to the
conduit system before it is connected to the terminal box of the
pump.
The pump must be connected to an external mains switch.
The pump requires no external motor protection.
The motor incorporates thermal protection against slow
overloading and blocking (IEC 34-11: TP 211).
When switched on via the power supply, the pump will start
pumping after approximately 5 seconds.
The number of starts and stops via the power
Note
Note
supply must not exceed four times per hour.

5.1 Supply voltage

Check nameplate voltage.
1 x 115 V ± 10 %, 50/60 Hz, PE.
1 x 208-230 V ± 10 %, 50/60 Hz, PE.
See pump nameplate for rated supply voltage
The voltage tolerances are intended for mains voltage variations.
They should not be used for running pumps at other voltages than
those stated on the nameplate.
12

Publicidad

Tabla de contenido
loading

Tabla de contenido