Descargar Imprimir esta página

Honeywell 4000 Serie Manual Del Usuario página 6

Actuadores de acoplamiento directo para válvulas
Ocultar thumbs Ver también para 4000 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

ML6984, ML7984 SERIES 4000 DIRECT COUPLED VALVE ACTUATORS
SIGNAL
SOURCE
ML7984
3
R
W
C
ML7984
3
R
W
C
ML7984
3
R
W
C
FUNCTION
1000
2-10 Vdc Direct Acting
1010
10-2 Vdc Reverse Acting
1
POWER SUPPLY PROVIDES OVERLOAD PROTECTION AND
DISCONNECT MEANS.
2
ALLOW UP TO 0.5 AMPS FOR EACH DEVICE. ACTUATORS AND
CONTROLLER CAN SHARE SAME TRANSFORMER PROVIDING THE VA
RATING OF THE TRANSFORMER IS NOT EXCEEDED AND PROPER
PHASING IS OBSERVED. DO NOT MIX A.C. AND D.C. POWER
SOURCES.
3
IN ML7984, "T5" AND "W" TERMINALS ARE CONNECTED INTERNALLY.
DEVICE IS COMPATIBLE WITH 3 CONDUCTOR WIRING.
4
USE CONFIGURATION DIP SWITCHES TO SELECT DEVICE FUNCTIONS:
DIRECT ACTING FUNCTION (ACTUATOR STEM MOVES DOWNWARDS
WITH SIGNAL INCREASES TO 10V/20MA) OR REVERSE ACTING
FUNCTION (ACTUATOR STEM MOVES UPWARDS WITH SIGNAL
INCREASES TO 10V/20MA).
5
ALWAYS TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES.
Fig. 11. ML7984 Wiring with 10 Vdc Analog Control Signal.
95C-10939EFS—03
2
T6
T5
2
1
T6
24 Vac
T5
OR
T6
28 Vdc
T5
2
T6
T5
DIP SWITCH CONFIGURATION
On (1)
4
Off (0)
1
3
4
2
On (1)
5
Off (0)
1
2
3
4
M25495
SIGNAL
SOURCE
L1
L2
FUNCTION
X000
4-20 mA Direct Acting
X010
20-4 mA Reverse Acting
1
POWER SUPPLY PROVIDES OVERLOAD PROTECTION AND
DISCONNECT MEANS.
2
ALLOW UP TO 0.5 AMPS FOR EACH DEVICE. ACTUATORS AND
CONTROLLER CAN SHARE SAME TRANSFORMER PROVIDING THE VA
RATING OF THE TRANSFORMER IS NOT EXCEEDED AND PROPER
PHASING IS OBSERVED. DO NOT MIX A.C. AND D.C. POWER
SOURCES.
3
IN ML7984, "T5" AND "W" TERMINALS ARE CONNECTED INTERNALLY.
DEVICE IS COMPATIBLE WITH 3 CONDUCTOR WIRING.
4
USE CONFIGURATION DIP SWITCHES TO SELECT DEVICE FUNCTIONS:
DIRECT ACTING FUNCTION (ACTUATOR STEM MOVES DOWNWARDS
WITH SIGNAL INCREASES TO 10V/20MA) OR REVERSE ACTING
FUNCTION (ACTUATOR STEM MOVES UPWARDS WITH SIGNAL
INCREASES TO 10V/20MA).
5
ALWAYS TURN POWER OFF BEFORE SETTING ANY DIP SWITCHES.
Fig. 12. ML7984 Wiring with 20mA Analog Control Signal.
6
ML7984
3
2
R
T6
W
T5
C
ML7984
3
2
R
T6
24 Vac
T5
W
C
T6
ML7984
3
2
T5
(SLAVE)
T6
R
W
T5
C
DIP SWITCH CONFIGURATION
Master actuator
Slave actuator
3
1
1
2
Master actuator
Slave actuator
1
1
3
2
1
L1
L2
OR
28 Vdc
On (1)
4
Off (0)
4
On (1)
5
Off (0)
4
M25496