11. Insert stripped end of red wire into the left lug.
Secure clamping screw.
12. Insert black wire into the right lug. Secure clamp-
ing screw.
13. Tighten each clamping screw with the appropri-
ate torque (see table).
Torque (in./lbs.)
Gauge
6
8
14. Properly secure lexible conduit at knockout on
angle and at supply side junction box. The wiring
is now complete.
red wire
Note: DO NOT plug in range at this time.
Three Wire Flexible Conduit Connection
The Four Wire Connection is preferred, but where lo-
cal codes and ordinances permit grounding through
neutral and/or conversion to four wire is impracti-
cal, unit may be connected to the power supply via a
three wire connection.
1. Disconnect electrical power at the breaker box.
2. Remove the terminal block cover to expose the
terminal block.
3. Remove the top nut, star washer, and round
washer from each post.
Note: DO NOT remove last round washer, last nut or
internal wire leads.
10
Torque (Nm)
35
3.95
25
2.82
green
ground
black wire
screw
white wire
green ground wire
4. Place one terminal lug (packaged with this man-
ual) on each post. Replace the star washer and
round washer and secure with 20" pounds of
torque.
5. Strip 8" (9.5 mm) of insulation from the end of
each wire.
6. Insert stripped end of white wire into the center
lug on top of the ground strap. Secure the clam-
ping screw.
lug
wire
7. Insert stripped end of red wire into the left lug.
Secure clamping screw.
8. Insert stripped end of black wire into the right lug.
Secure clamping screw.
9. Tighten each clamping screw with the appropriate
torque (See table below).
Gauge
Torque (in./lbs.)
6
8
10. Properly secure lexible conduit at knockout pa-
nel on range and at supply side junction box. The
wiring is now complete.
green ground screw
Note: DO NOT plug in range at this time.
3/8 "
clamping screw
Torque (Nm)
35
3.95
25
2.82