Descargar Imprimir esta página

ABB PSTX30 Manual Del Usuario página 16

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 84
Parameter name
13.1 EOL mode
13.2 EOL class
13.3 EOL dual class
13.5 EOL operation
13.10 Locked rotor operation
14.5 Current underload operation
15.4 Over voltage operation
15.7 Under voltage operation
16.2 Phase reversal operation
16.9 By-pass open operation
18.5 Earth fault trip time
18.7 Earth fault operation
Parameter name
20.1EOL level
20.3 EOL warning
20.7 Locked rotor
20.9 Thyristor overload
21.5 Current underload
22.4 Over voltage
22.8 Under voltage
23.1 EOL time-to-trip
23.4 THD(U) level
23.6 THD(U)
24.1 Number of starts limit
24.3 Number of starts
23.8 Short circuit
16 Softstarters Type PSTX30...PSTX1250 User Manual short form 1SFC132082M9901
Protections
Setting range
Normal/Dual
10 A, 10, 20, 30
10 A, 10, 20, 30
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
Off, Stop-Manual,
Stop-Automatic, Indication
0,1s ... 10,0s
Off, Stop-Manual,
Stop-Automatic, Indication
Warnings
Setting range
40 ... 99%
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
1...10%
On/Off
1 ... 65535
On/Off
On/Off
Default value
Normal
10
20
Stop-Manual
Off
Off
Off
Off
Off
Indication
0,5s
Off
Default value
90%
Off
Off
Off
Off
Off
Off
Off
10%
Off
65535
Off
Off

Publicidad

loading