Step 4: L1 off, L2 blinks, L3 and L4 off.
L5 will turn on if the selected temperature is between
–5°C and 15°C.
Step 5: L1 off, L2 blinks, L3 off, L4 blinks.
L5 will always turn on.
Step 6: L1 off, L2 and L3 blink, L4 off.
L5 will turn on if there is 24Vca in the IN1 terminal
(Pressostat input).
Step 7: L1 off, L2, L3 and L4 blink.
L5 will turn on after 1 second and will remain on during
5 seconds. The IN1-OUT1 contact will remain closed
while L5 is ON (Contact for the compressor contactor
handling).
SPECIFICATIONS:
Power voltage:
Maximum consumption:
Operating temperature:
Digital inputs (IN1, IN4, IN5, IN6)
Analog inputs (A3,A4) Sensor type
Temperature setting input
Saídas digitais
Control board dimensions
Control front dimensions
Temperature setting dimensions
Long cable in front of control
Long temperature setting cable
38
Maximum permanent voltage
Input current
Maximum de-activation voltage
Minimum activation voltage
Answer time 0 to 24Vca
Answer time 24 to 0Vca
Temperature setting
• OUT1
Maximum voltage
Maximum current
• OUT2
Maximum voltage
Maximum current
Step 8: L1 blinks, L2, L3 and L4 off.
L5 will turn on after 1 second and will remain in this
status. The IN2-OUT2 contact will remain closed while
L5 is ON (Contact to handle the solenoid valve).
Step 9: L1 blinks, L2 and L3 off, L4 blinks.
L5 will turn on if there is 24 Vca in the IC3 terminal
(Input for the remote control contact).
Step 10: L1 blinks, L2 off, L3 blinks, L4 off.
L5 will turn on if there is 24 Vca in the IC4 terminal
(Input for the ON/OFF remote control).
24V ±15%, 50Hz or 60Hz.
200mA
-20°C a +60°C
80Vca ou 60Vcc
0,65mA @ 24Vca
(for IN1 add current in OUT1)
1Vca
4Vca
0,25s
1s
NTC de 5kW @ 25°C
Lineal potentiometer
80Vca
16A resistive charge
250Vca
16A resistive charge
121 x 123 mm
100 x 100 mm
45 x 35 mm, high: 35mm with handle
included
300mm
250mm