3.4
EXTERNAL SENSOR (fig. 15)
If there is an external sensor, the heating
settings SET can be taken from the climatic
curves according to the external tempera-
ture and, in any case, limited to with the
range values described in point 3.2 (para-
meters PAR 13 and PAR 14).
The climatic curve to be set can be selected
from a value of 3 and 40 (at step 1).
Increasing the steepness of the curves of
fig. 15 will increase the output temperature
as the external temperature decreases.
3.5
CARD FUNCTIONING
The electronic card has the following func-
tions:
– Antifreeze protection of the heating cir-
cuit.
– Ignition and flame detection system.
– Control panel setting for the power and
the gas for boiler functioning.
– Anti-block for the pump which is fed for
a few seconds after 48 hours of inacti-
vity.
– Chimney sweep function which can be
activated from the control panel.
– Temperature which can be shifted with
the external sensor connected.
It can be set from the control panel.
– Automatic regulation of the ignition
power
and
maximum
Adjustments are managed automati-
cally by the electronic card to guaran-
tee maximum flexibility in use of the
system.
– Interface with the following electronic
systems: remote control CR 73 o CR
63, with coupling kit card expansion
code 8092240.
3.6
TEMPERATURE
DETECTION SENSOR
Table 3 gives the values of the electrical
element (
) obtained on the heating and
sanitary water sensors according to the
variations in temperature.
The C.H. sensor (SM1/SM2) is of type to
double sensing element with function safety
thermostat.
When the heating sensor (SM1/SM2) is
interrupted, the boiler will not function
for both services.
With the D.H.W. sensor (SS) interrupted,
the boiler functions only in modality
D.H.W.
TABLE 3
Temperature (°C)
Resistance (Ω)
20
30
40
50
60
70
80
84
ATTENTION: curves are calculated at an ambient temperature of
20°C. Using the
the set ambient by ± 5°C for which the curve is calculated.
heating.
3.7
ELECTRONIC IGNITION
Ignition and flame detection is controlled by
a single electrode on the burner which gua-
rantees reaction in the case of accidental
extinction or lack of gas within one second.
3.7. 1
Functioning cycle
Burner ignition occurs within max. 10
seconds after the opening of the gas valve.
Ignition failure with consequent activation of
block can be due to:
– Lack of gas
The ignition electrode persists in dischar-
ging for max. 10 seconds. If the burner
does not ignite, the anomaly is signalled.
This can happen the first time the boiler
is switched on after a long period of inac-
tivity due to the presence of air in the gas
pipes.
It can be caused by a closed gas tap or by
a broken valve coil (the interruption does
not allow for opening).
– The electrode does not discharge.
In the boiler, only the opening of the gas
to the burner can be detected. After 10
seconds the anomaly is signalled.
12.090
It can be caused by an interruption in the
8.313
electrode wire or if it is incorrectly ancho-
5.828
red to the connection points.
4. 1 61
Or the electrode may be earthed or
3.021
strongly worn: it must be replaced.
2.229
Or the electronic card may be defective.
1.669
key on the control panel, the user can change
In the case of a sudden lack of voltage, the
burner will immediately switch off. When
voltage returns, the boiler will automatically
start up again.
3.8
This is a safety measure against the return
of the fumes into the environment due to
an inefficient or partially blocked chimney
(7 fig. 3).
It reacts by blocking the functioning of the
gas valve when the fumes are continually
forced back into the environment, in a
quantity that can be dangerous. If the boiler
repeatedly stops, it will be necessary to
carefully check the chimney, and to carry
out all modifications and take all measures
necessary to restore it to an ef ficient
working state. After every intervention car-
ried outon the device, check correct func-
tioning. In the case of replacement, use only
original spare parts.
3.9
The pressure switch is calibrated by the
manufacturer at the following values:
0.62 - 0.72 H
0.45 - 0.55 H
which can guarantee boiler functioning also
with aspiration and discharge pipes of the
maximum length allowed.
Fig. 15
FUMES THERMOSTAT
"25 OF"
FUMES PRESSURE SWITCH
"25-30 BF" (fig. 16)
O for vers. "25 BF"