Typical Installation Using
3
1. Adequate clearances around floor furnace.
2. Draft Diverter 6" from combustibles.
3. Adequate clearances around vent pipe.
4. Horizontal vent pipe sloping upward 1/4" per foot.
5. Pipe supported with metal straps.
6. Adequate height of vent system.
7. Listed vent cap.
5
4
3
The gas piping system must meet the requirements of local codes or the specifications of the servicing gas supplier. It must have
adequate capacity to supply the floor furnace and any other appliance within the home with enough gas to maintain the full rated
capacities without excessive pressure drop when all appliances are operating at full rate.
GAS PIPE SIZES - CAPACITY NATURAL GAS ○
Length
Inside Pipe Diameter
of Pipe -
Feet
1/2"
3/4"
10
132,000
278,000
20
92,000
190,000
30
73,000
152,000
40
63,000
130,000
50
56,000
115,000
60
50,000
105,000
○ Based on heating value of 1,000 value of 1,000 BTU per cubic
foot (specific gravity of 0.6) at 0.5 PSIG and a pressure drop
of 0.3 inch water column.
Support the piping or tubing at regular intervals with metal pipe strapping. See charts below.
Nominal Steel Pipe Size
1/2"
3/4" or 1"
• Where local conditions include earthquake, tornado, unstable ground or flood hazards, give special consideration to increased
strength and flexibility of piping supports and connections. Consult local authorities for recommendations.
• All unused openings in the piping system must be securely closed gas-tight.
CONNECTING THE VENT
Class "B" Vent Pipe
2
1
GAS SUPPLY AND PIPING
1"
520,000
350,000
Capacity
285,000
BTU
245,000
Per Hr.
215,000
Input
195,000
Spacing of Supports
6'
8'
If more than one gas appliance is vented through a
FIG. 9
common vent system, the vent should be increased
in size to accommodate the increased load. Consult
your local code or the tables in the latest edition
of NFPA54 / ANSI.Z223.1 for the correct size. If
no local codes apply, use the following alternate
method for sizing a vent connected to more than one
appliance. The effective area of the vent must be
not less than the area of the largest vent connection
plus 50 percent of the areas of additional draft hood
outlets.
The
homeowner
workmanship and the neat installation usually
functions better than the sloppy one. Double check
your work to verify that all clearances around the
floor furnace and vent system are adequate and
that the vent system is installed to code or pipe
manufacturers specifications. See Figure 9.
GAS TUBING AND PIPE SIZES - CAPACITY PROPANE GAS *
Copper Tubing
Length
Outside Diameter**
of Pipe /
Tubing Feet
1/2"
10
92,000
329,000
20
62,000
216,000
30
50,000
181,000
40
41,000
145,000
50
37,000
131,000
60
35,000
121,000
* Undiluted Liquefied Petroleum Gas at 11 inches water column inlet pressure.
Based on a pressure drop of 0.5 inches water column.
** Copper tubing must comply with limitations of NATIONAL FUEL GAS CODE
reference 2.6.3 metallic tubing.
*** Steel pipe should be of at least standard weight (Schedule 40).
Nominal Size of Tubing O.D.
1/2"
5/8" or 3/4"
Page 9
appreciates
neatness
Steel Pipe
Inside Diameter***
3/4"
1/2"
3/4"
275,000
567,000
189,000
393,000
152,000
315,000
129,000
267,000
114,000
237,000
103,000
217,000
Spacing of Supports
4'
6'
Back to Index
in
Capacity
BTU
Per Hr.
Input
1017826-A