USER INSTRUCTIONS
Control logic (2 or 4 ways)
Press the button key
access, the current parameter value is displayed. Change
the thermostat control logic (0 = common logic; 1 =
separate logic) via the circular touch slider or the push-
button
. The joint control logic is associated with 2-way
systems, with a single valve for heating/cooling. The
separate control logic is associated with 4-way systems,
with two valves, one for heating and the other one for
cooling. The parameter is visible only if the device is
configured with Easy Controller. To confirm the set value,
press the
button key within thirty seconds; expiry of
the timeout (30 seconds) or pressing the push-button
result in exiting the change page without saving it.
Temperature adjustment control algorithm
Press the button key
access, the current parameter value is displayed. Change
via the circular touch slider or the push-button
control algorithm (0 = two ON/OFF points; 1 = PWM
proportional-integral; 2 = fan coil with 3 ON/OFF speed
control for heating
on the type of operation and control logic set. The parameter
is visible only if the device is configured with Easy
Controller. To confirm the set value, press the
key within thirty seconds; expiry of the timeout (30 seconds)
or pressing the push-button
page without saving it.
56
to access value change; after the
to access value change; after the
, cooling
or both
result in exiting the change
the
, based
button