7.3.3 Manual call point Alarm threshold setting at the Microswitch.
The switch with number 5 allows modification of the Manual call point threshold.
Microswitch
CONFIGURATION
1
2
3
4
5
6
7
8
0
1
1
2
3
4
5
6
7
8
7.3.4 Last Zone operation mode setting at the Microswitch
The switch with number 6 allows modification of the Zone 3 operation mode. The Zone 3 can
work as a normal detection zone or for the monitoring of the Extinguishing system receiving
signal from a pressure switch.
In this last case, closing the pressure switch with a serial resistance of 470 Ω, gives indication of
Open line fault at Zone 3 of the Control panel instead of an alarm.
Microswitch
CONFIGURATION
3
7
8
1
2
4
5
6
0
1
1
2
3
4
5
6
7
8
11.5 Extinguishing operation mode setting at the Microswitch.
The switch with number 7 and 8 allow modification of the Extinguishing operation mode which
means Control panel can be adjusted better to the circumstances that are required for the
system.
Microswitch
CONFIGURATION
1
2
3
4
5
6
7
8
0
0
1
8
1
2
3
4
5
6
7
0
1
1
2
3
4
5
6
7
8
0
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
Conventional Fire Detection and Fire Alarm Control Panel
Manual call point threshold at 8 V.
(Default Control panel setting)
Manual call point threshold at 12 V
Zone 3 in Standard Fire detection Mode.
► Detector Alarm is indicated as Detector Alarm.
► Manual call point Alarm is indicated as Manual call point Alarm.
(Default Control Panel setting)
Zone 3 in Fault signaling Mode.
► Detector Alarm is indicated as Open line Fault.
► Manual call point Alarm is indicated as Open line Fault.
Extinguishing system at Standard mode.
► The Advace Warning Extinguishing Output (R1) is activated with
the first extinguishing zone (zone 1 or 2) in in Alarm status as
explained at chapter 5 of the Manual.
(Default Control Panel setting)
Extinguishing System at Consecutive Mode.
► With one extinguishing zone in alarm status (zone 1 or 2), the
Advance
Warning
Extinguishing
intermittently (1 second turn on, 1 second turn off).
► With two extinguishing zones in alarm status (zone 1 and 2), the
Advance
Warning
Extinguishing
intermittently (0,25 seconds turn on, 0,25 seconds turn off).
► With two extinguishing zones in alarm status (zone 1 and 2), the
Advance
Warning
Extinguishing
continuously when the delay of the Extinguishing Output (R2) has
finished.
Extinguishing System in Simultaneous Mode.
► The Advance Warning Extinguishing Output (R1) is activated
continuously with the two extinguishing zones (zone 1 and 2) in
alarm status.
FIRE PROTECTION MANUFACTURER
CLVR02EXT
DESCRIPTION
DESCRIPTION
DESCRIPTION
Output
(R1)
Output
(R1)
Output
(R1)
is
activated
is
activated
is
activated
47