Lowara ecocirc PRO 15-1/65 Instrucciones Para La Instalación Y El Uso página 18

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 37
4.
Technical Specifications
High-efficiency, shaftless spherical motor with ECM technology
Rated voltage
Frequency
Power consumption
Ingress Protection
Insulation class
Protection class
Max. system pressure
Max. system temperature
Min. ambient temperature
5.
Pump Curve (see figure 2)
6.
Installation Sequence (see figure 3)
WARNING
Description for figure 3:
1 - Water heater
2 - Check valve
3 - Ball shut-off valve
4 - Circulation pump type ecocirc PRO
7.
Installation
The pump may not be installed in areas where there is a danger of
explosion
The pump may not be used to pump flammable, or explosive liquids.
When using versions with pump housing 70, use the
LOWARA RV ½" check valve. This prevents water from
flowing through the pump backwards when the faucet is
opened, thus causing damage. When using valves other than
RV ½", pay attention to appropriate closing pressure. Install
the RV ½" check valve in the direction of flow, so that the
arrows on the pump housing and on the check valve point in
the same direction.
We recommend that you install a ball shut-off valve before the
pump so the pump can be replaced at a later time without
completely draining the system.
Pumps with housings #10 and #94 already contain an
integrated check valve and a ball shut-off valve in the pump
housings. (The check valve opens and closes automatically;
when the handle of the ball shut-off valve is perpendicular to
the pipe direction, the valve is closed).
200-240 V
50/60 Hz
2 ... 27 W
IP 44 , IP 42 with timer
155 (F)
I
1 MPa (10 bar)
65 °C
Not freezing/ non-condensing
18

Publicidad

Tabla de contenido
loading

Tabla de contenido