10.2 - AUTOMATIC SENSITIVITY
ADJUSTMENT
1. Press and hold the OK button until the display shows
2. Release the OK button: the display shows
(press OK only if you want to exit this menu)
i
3. Press the
key: the display shows
4. Press the OK button to start the procedure: the message
SEnS
flashes on the display and the gate performs a full
closing cycle until reaching the end of stroke (complete
opening phase and complete closing phase).
5. When the procedure is finished, the display shows the control
panel
m
ATTENTION: if the control unit receives a START
command during the automatic learning procedure, the
procedure is aborted and the control unit stores the partial
data determined.
-SEn
ESC
SEnS
-SEn
ESC
SEnS
SEnS
- 37 -
10.3 - LOADING THE DEFAULT
PARAMETERS
If necessary, it is possible to restore all parameters to their
standard or default values (see the final summary table).
m
PLEASE NOTE: This procedure results in the loss of all
customised parameters.
1. Press and hold the OK key until the display shows
2. Release the OK key: the display shows
OK key if it is desired to exit this menu)
i
3. Press the
key: the display shows
4. Press the OK key: the display shows
i
5. Press the
key: the display shows
6. Press the OK key: all parameters are overwritten with their
default values (see Chapter 12), the control units exits
programming mode and the display shows the control panel.
-dEF
no
Si
-dEF
ESC
(only press the
dEF
no
YES
ESC
dEF.