18
Cycles Available
Selects number of available cycles.
1...15 cycles. > Default: 15.
19
Block Programming Cycles
Selects number of cycles that the user cannot modify (these can be pre-
programmed by the manufacturer/installer to avoid wrong progamming).
Ex.: selecting 3 the programming of the fi rst 3 cycles is locked.
0...15 locked cycles. > Default: 0.
20
Waiting Time Step End
Selects time for step end waiting in hh.mm.
00.00 Step end waiting excluded
00.01...24.00 hh.mm. > Default: 01.00.
21
Max. Gap Step End
Selects max. gap for step end waiting activation. When the diff erence
between setpoint and process is lower than this parameter, the controller
switches to the next step (also without waiting for the time programmed
on parameter 36
0...200 degrees. > Default: 5.
22
Recovery Interrupted Cycle
Enables the interrupted cycle recovery function.
0 Cycle recovery disabled
1 Cycle recovery enabled with automatic gradient. > Default.
2...1000 degrees/hour. Select recovery gradient.
)
ATR902 - User manual
27