Alarm 1 Action Type
Defi nes alarm action type on operating cycle

(No Action). Changes only output related to the alarm. > Default.

(End Cycle Signal). Cycle ends (STOP) with acoustic and visual si-
gnalling. Changes output related to the alarm, buzzer sounds and
on display fl ashes

(Audible Signal), Only acoustic signalling: buzzer sounds.

2nd level parameters (for expert operators)

11.2

40
Conversion Filter
Adc fi lter: number of means on analogue-digital conversions.
1...15 samplings. > Default: 10.

41
Starting Setpoint
Enables cycle starting setpoint to guarantee the programmed gradient
for the fi rst step.

(Disabled) Cycle starting setpoint disabled.

(Enabled) Cycle starting setpoint selectable by the user.

(Enabled Ambient Temperature) Fixed cycle starting setpoint
(25°C). > Default.

42
Chronometer
Enables chronometer: with cycle in execution it shows the time elapsed
from cycle start; with cycle in STOP it visualizes the duration of the last
cycle. At switch-off it is reset to zero.

(Disabled) > Default

(Enabled)

43
Power Consumption
This parameter defi nes the power of the heating group controlled by the
device. If the value selected is diff erent from 0.0, pressing STEP (when no cycle
is in execution), it is possible to visualize the employed power consumption
(Kwatt/hour) of the last cycle. At switch-off value is lost.
0.0...999.9 KWatt/h. > Default 0.0.
