5
Wiring the device
Important notes
5
Wiring the device
5.1
Important notes
Danger!
Dangerous voltage
All power terminals remain live for at least three minutes after mains
disconnection.
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
Danger!
Dangerous voltage
The discharge current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Protective measures:
ƒ
Stop!
The device contains components that can be destroyed by electrostatic
discharge!
Before working on the device, personnel must ensure that they are free of
electrostatic charge by using appropriate measures.
60
Death or severe injuries when touching the power terminals.
Wait for at least three minutes before working on the power terminals.
Check that all power terminals are deenergised.
Death or severe injuries when the device is touched in the event of a fault.
Implement the actions required in the EN 61800-5-1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
2
≥ 10 mm
or PE conductor must be connected twice)
EDK94SH104 DE/EN/FR/ES/IT 4.1