Sunways NT 10000 Manual Del Usuario página 145

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Error
Causes
Objects have been deposi-
ted on the heat sink,
obstructing the convection.
Errors 010 to 012
The grid voltage of the
Grid under-
injecting phase is too low.
voltage 1-phase
The Solar Inverter monitors
the lower and upper admis-
sible grid voltage limits. If
the voltage drops below the
lower limit (U
the Solar Inverter will auto-
matically switch off and will
only restart when the volta-
ge value rises above the
lower limit again. The shut-
down can already be trig-
gered if the voltage drops
below the lower limit for a
short time.
Errors 013 to 015
The grid voltage of the
Grid overvoltage
injecting phase is too high.
1-phase
The Solar Inverter monitors
the lower and upper admis-
sible grid voltage limits.
Remedies
Remove the objects.
Ask your power supply company about
the stability and design of the grid.
Check the rating of your grid connection
(power meter) or the grid injection
point to your power supply company.
= 184 V),
min
Ask your power supply company about
the stability and design of the grid.
145