DRIVE CONFIGURATION
Motor Type Selection
DRIVE CONFIGURATION
To adjust system settings, make sure power is off and remove the cover.
MAX AMPS
1/2
3/4
1
1.5
1
2
3
4
SW1
Contact with hazardous voltage could result in death or serious injury.
•
Do not attempt to modify DIP switch or potentiometer settings until power has been removed and 5
minutes have passed to allow internal voltage to discharge.
•
Do not power on or use the drive with the cover removed.
Motor Type Selection
Select Motor Type (DIP SW1 – Position 6)
When using a Franklin Electric Submersible motor, SW1 – Position 6 must be set to SUB (down).
When using a Surface/Centrifugal style pump, SW1 – Position 6 must be in the CEN (up) position.
Select Submersible Motor Phase (DIP SW1 – Position 7)
When using a Single phase 3-wire submersible motor, position 7 must be set to MD 3W (up).
When using a Three phase submersible motor, position 7 must be set to SD 3P (down).
Submersible Motor Horsepower Setting (DIP SW1 – Positions 1–5)
Select a single DIP switch from SW1, position 1 - 5 that corresponds with the submersible motor/pump HP
being used and place it in the U
on the shield.
Selecting none or more than one switch will result in an Invalid Configuration fault.
Surface Pump Maximum Amps Setting (DIP SW1 – Positions 1–5)
When the drive is configured to operate a surface style pump, SW1 – Positions 1-5 must be used to set the
correct MAX AMPS motor overload current to properly protect the motor. Refer to
Positions 1–5)" on page 23
NOTE: DIP SW1 – Position 8 is not used at this time.
22
FAST
MED
MD
RÁPIDO
MEDIO
2
CEN
3W
XDCR
VITE
MOYEN
5
6
7
8
1
2
3
SUB
SD
PS
3P
position. The corresponding HP values are printed above the SW1 diagram
P
for more information.
SLOW
LENTO
FW
LENT
DD
VER
SF
BP
4
5
6
7
8
1
2
SW2
"Maximum Amps (DIP SW1 –
LT
AB
BD
HZ
3
4
5
6
7
8
ST
SW3
+
-