DRIVE CONFIGURATION
Pressure Input Selection (DIP SW2 – Position 1)
Pressure Transducer: When using a 4-20 mA pressure transducer, the desired system pressure is
set by using the pressure setpoint adjustment knob. The knob is factory set to 50% of the trans-
ducer range and is adjustable from 5% to 95% in 5% increments. This allows any range of pressure
transducer to be used. Refer to the indicator lines surrounding the switch and the corresponding
legend printed on the shield when setting the desired pressure setpoint.
Refer to the table below for percentage to PSI conversions for popular transducer ranges.
The pressure setpoint must be adjusted with the drive powered OFF. The new setting will
not take effect until the drive power is cycled.
NOTE: This knob is only compatible with an optional 4-20 mA pressure transducer. A
pressure transducer must be installed in the system, and DIP SW2 Position 1 must be in
the XDCR (up) position.