Firmware Updates; Firmware Version Readout - Franklin Electric SUBDRIVE UTILITY UT3P Manual Para Propietarios

Ocultar thumbs Ver también para SUBDRIVE UTILITY UT3P:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Firmware Updates

Firmware Version Readout

The drive is able to use the display LEDs to perform a flash sequence to indicate the version of firmware
currently installed on the drive in XYZ format. Follow this procedure to identify the firmware version:
1.
Remove power from the drive and allow 5 minutes for internal voltage to dissipate.
2. Remove the drive cover.
3. Place DIP SW2 – Position 8 in the FW VER (up) position.
4. Reinstall the drive cover before applying power to the drive.
5. Apply power to the drive. The firmware readout procedure will begin automatically as follows:
• All three (3) LEDs will rapidly flash together to indicate that the readout procedure is starting.
• The Power LED (top/green) will slowly flash at a rate of 1 flash/second. The number of flashes indi-
cates the X value of the drive firmware version.
• The Running LED (middle/green) will slowly flash at a rate of 1 flash/second. The number of flashes
indicates the Y value of the drive firmware version.
•The Fault LED (bottom/red) will slowly flash at a rate of 1 flash/second. The number of flashes indi-
cates the Z value of the drive firmware version.
•These steps will repeat indefinitely.
6. Remove power from the drive and allow 5 minutes for internal voltage to dissipate.
7.
Remove the drive cover.
8. Place DIP SW2 – Position 8 in the OFF (down) position.
9. Reinstall the drive cover.
10. Power on the drive. The drive will return to normal operation.
MAINTENANCE
Firmware Updates
35

Publicidad

Tabla de contenido
loading

Tabla de contenido