SAFETY INSTRUCTIONS
Product Specific Precautions
Product Specific Precautions
High voltages capable of causing severe
injury or death by electrical shock are
present in this unit.
•
Do not remove VFD cover for wiring or periodic inspec-
tions while power is applied, or the unit is in operation.
•
Capacitors inside the drive can still hold lethal voltage
even after power has been disconnected—ALLOW 5 MIN-
UTES FOR DANGEROUS INTERNAL VOLTAGE TO DIS-
CHARGE BEFORE REMOVING COVER OR WORKING WITH
INTERNAL COMPONENTS.
•
Perform wiring after VFD has been mounted. Otherwise,
electric shock or bodily injury can occur.
•
Do not apply power to a damaged VFD or to VFD with
missing parts.
•
Do not use VFD if power or motor cable is damaged.
•
Do not handle the VFD or control devices with wet hands
or when standing on a wet or damp surface, or in water.
6
Risk of damage to drive or other equipment.
•
Install and wire drive according to the instructions in this
manual.
•
Take protective measures against ESD (Electrostatic Dis-
charge) before touching control boards during inspection,
installation or repair.
•
This product is recommended for use with Franklin Electric
4-inch submersible motors as specified in this manual.
Refer to
"Common Specifications" on page
unit with any other Franklin Electric motor or with motors
from other manufacturers may result in damage to both
motor and electronics.
•
In applications where water delivery is critical, a replace-
ment pressure sensor and/or back-up system should be
readily available if the drive fails to operate as intended.
37. Use of this