PLACE | Wall Sensor
Wall sensors with pre-installed adhesive tape (for screws from optional hardware package, refer to page 11)
-
Determine placement of wall sensor:
Place wall sensor on the wall 10' (3.05m) above the floor or on the ceiling if lower than 10' (3.05m).
Maximum placement height is 12' (3.65m).
It's best to dry fit the sensor to its proper location prior to permanently affixing the mount.
When acoustic tiles are present, mount to ceiling using adhesive tape and an acoustic tile staple.
(Refer to page 11.)
Be sure to allow at least 2" from the end of the sensor to any obstacle to allow clearance to
remove the sensor from the mounting bracket.
-
Remove backing from adhesive strip
-
Attach sensor/mounting bracket to surface
-
Apply force to mounting bracket for at least 15 seconds to ensure bonding to surface. Full bonding time is 72 hours.
-
Align the tab on the sensor to the corresponding slot on the mounting bracket ()and insert sensor into
the bracket until it locks in place.
Mounted to wall
(side view)
wall
Distance to floor ±3" (75mm)
Mounted to ceiling
(side view)
ceiling
wall
Sensor(s) SHOULD NOT be able to sense
motion outside of the room; i.e., the "cone of
vision" should not fall outside of room/doorway.
Wall sensors should always be adhered at 10'
high or ceiling height (whichever is lower)
wall
NOTICE
Page 7 of 41
1083528001 Rev B