Switching On And Off; Removal; Confi Gurable Limit Values And Operational Settings - Sputnik Engineering SolarMax 2000S Documentación Del Dispositivo

El inversor para sistemas de electricidad solar conectados a la red
Ocultar thumbs Ver también para SolarMax 2000S:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

3.4 Switching on and off

All SolarMax inverters operate fully automatically and maintenance-free. The
isolating switches between the solar generator, the inverter and the 230 V mains
supply remain on at all times. SolarMax will start and transfer power to the
230 V grid when the irradiance is high enough. Otherwise the device remains in
standby mode and is thus available for grid feeding at all times. Overnight the
electronic system is disconnected from the mains.
Voltage may only be applied on the DC and AC side of the SolarMax with
the device closed.
Switching on:
Switch on DC insulation switch.
The graphics display powers up.
During the night or at times of insuffi cient irradiance the graphics display turns
itself off (no energy consumption).
Switch on the AC isolating switch (may be fused).
Switching off:
Switch off the AC insulation switch.
Large arcs may be generated if connectors are disconnected on the DC
side during operation.
Switch off the DC insulation switch.
Graphics display switched off.

3.5 Removal

The device does not have to be opened for demounting.
The inverter must be de-energised. First disconnect the device from the mains
on the AC side via the AC line protection breaker or the fuse. Then open the
DC insulation switch in order to disconnect the inverter from the solar generator
fi eld. Now remove the connectors.
Before releasing the screws ensure that the bottom of the device (heat sink) has
cooled suffi ciently to allow the device to be safely handled.
Release the two locking screws on the left and right and remove the inverter
from the mounting.
65
3.6 Confi gurable limit values and operational settings
In the SolarMax S series the following parameters can be set manually via the inter-
face with the MaxTalk software. The settings are password-protected. A password
application form can be ordered via the SolarMax hotline. The password is only
made available to installers who sign the form. The password is not made available
to private individuals or system operators.
Parameter
Unit
Regional settings
DE/CH
IT
ES
Vac max
V
V
264.5
264.5
274
274
253
253
Vac min
V
V
184
184
186
186
196
196
f max
Hz
Hz
50.2
50.2
50.3
50.3
50.2
50.2
f min
Hz
Hz
47.5
47.5
49.7
49.7
49.8
49.8
df/dt max
Hz/s
Hz/s
0 (Inactive)
0 (Inactive)
Vac 10min max
V
V
253
253
0 (Inactive)
0 (Inactive)
Ierr max
mA
mA
300
300
300
300
300
300
Iac mean max
A
A
1 1
0.5% of
0.5% of
1 1
Iac rated*
Iac rated*
Restart delay
0 0
10 10
s
s
0 0
Pac max
W
W
1980
1980
1980
1980
1980
1980
SM2000S
Pac max
W
W
2750
2750
2750
2750
2750
2750
SM3000S
Pac max
W
W
4180
4180
4180
4180
4180
4180
SM4200S
Pac max
W
W
5060
5060
5060
5060
5060
5060
SM6000S
Iac max
A
A
12 12
12 12
12 12
SM2000S
Iac max
A
A
12 12
12 12
12 12
SM3000S
Iac max
A
A
19 19
19 19
19 19
SM4200S
Iac max
A
A
22 22
22 22
22 22
SM6000S
* Iac max = 1.1 x Iac rated
The set values can be queried via the display in the main menu (see section 5.4)
Password-
protected
FR
Other
setting
264
264
300
300
184...300
184...300
196
196
184
184
50.5
50.5
55 55
45...55
45...55
49.5
49.5
45 45
0.1...1
0.1...1
264
264
264.5
264.5
243.8...264.5
243.8...264.5
300
300
300
300
50...300
50...300
1 1
1 1
0.05...1
0.05...1
0 0
0 0
0...600
0...600
1980
1980
1980
1980
990...1980
990...1980
2750
2750
2750
2750
1375...2750
1375...2750
4180
4180
4180
4180
2090...4180
2090...4180
5060
5060
5060
5060
2530...5060
2530...5060
12 12
12 12
6...12
6...12
12 12
12 12
6...12
6...12
19 19
19 19
9...19
9...19
22 22
22 22
11...22
11...22
en
66

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Solarmax 3000sSolarmax 4200sSolarmax 6000s