Shutdown After Overload; Operating Faults - MGE UPS Systems Pulsar EX15 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 77

shutdown after overload

To acknowledge an overload fault, place the
button 3 in the released position, check the
power absorbed by your loads, disconnect
non-priority loads and restart Pulsar EX by
placing the button 3 in the depressed
position.
1a
flashing/overload
-
+
off/power on
1e
-
%
+
flashing/power off
1f
off/load de-energized
intermittent beeps
MGE UPS SYSTEMS

operating faults

UPS faults
c UPS not fitted with an "automatic
bypass" module:
1b
flashing/device fault
-
+
off/power on
1e
-
%
+
flashing/power off
1f
off/load de-energized
intermittent beeps
Your loads are no longer supplied. Call
the after-sales service.
c UPS fitted with an "automatic bypass"
module:
1b
flashing/device fault
-
+
1e
off/power on
-
%
+
flashing/load in
1f
"automatic
bypass"
intermittent beeps
Your loads are supplied by the AC power.
Call the after-sales service.
Pulsar EX : 51032306XT/BB
operating faults
battery fault
The battery is tested during the Pulsar EX
start-up procedure and then automatically,
for instance once a day (frequency may be
set using EX Driver).
If the battery is faulty, the display will show:
1c
flashing/device fault
-
+
off/power on
1e
-
%
+
flashing/power off
1f
on/load energized
silence
c check that the battery switch 7 on
Pulsar EX, and the circuit-breakers 32 on
Pulsar EXB (if this option is fitted) are
closed. Otherwise close them;
c the indicator light 1c will stop flashing at
the next test (i.e. within 24 hours at the
most);
c otherwise, call the after-sales service.
35