Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 77

reconnecting Pulsar EX

Operating mode:
c take the "manual bypass" module 25 or
31 and connect it behind Pulsar EX;
c screw on this module using the 2 screws
24 ;
c plug the cable 26 into the connector 12
on Pulsar EX;
c close the battery circuit-breaker 7 on
Pulsar EX (as well as the circuit-breakers
32 on the Pulsar EXB battery extension
modules if fitted): "l" position;
c with the "manual bypass" switch 28 set
to "BY-PASS", depress the button 3 ;
c check after 15 seconds that Pulsar EX
has started properly and that the following
indications are obtained:
1a
1c
to
off
-
+
flashing/operation on
1d
"manual bypass"
off/power on
1e
-
%
+
1f
flashing
intermittent beeps
38
c if the indicator lights are in a status other
than that indicated, do not switch the "manual
bypass" and contact our after-sales service;
c switch the "manual bypass" 28 from the
"BY-PASS" position to the intermediate
position (see figure 10).
The following indications are obtained:
1a
to
1d
n/a
-
+
1e
off/power on
-
%
+
flashing/load in
1f
"automatic
bypass"
intermittent beeps
c switch the "manual bypass" 28 from the
intermediate position to the "NORMAL"
position: operation is now normal and the
following indications are obtained:
indicate battery state
1a
1d
to
-
+
off/power on
1e
-
%
+
flashing/power off
1f
on/load energized
silence
Pulsar EX : 51032306XT/BB
"manual bypass" switch 28
NORMAL
"BY-PASS" position
NORMAL
intermediate position
NORMAL
"NORMAL" position
Figure 10
MGE UPS SYSTEMS
BY-PASS
BY-PASS
BY-PASS

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pulsar ex20Pulsar ex30Pulsar ex40

Tabla de contenido