5
Wiring the device
Wiring
Wiring of control connections
5.3.4
Wiring of control connections
24 V supply
Terminal X11
9400SSP000X2
Terminal data
Flexible
With wire end
ferrule
Stripping length / contact length: 10 mm
Digital inputs, digital outputs
Terminal X12
SSP9400X12
Terminal data
Flexible
With wire end
ferrule
Stripping length / contact length: 10 mm
54
Labelling
Description
GE
GND external supply
24E
24 V external supply through safely separated power supply unit
(SELV/PELV)
Required for mains-independent power supply of control electronics.
IEC 61131-2, 19.2 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 1.4 A
Starting current: 4 A for 100 ms
SB
Reserved
Conductor cross-section
2
[mm
]
0.2 ... 2.5
Labelling
Description
GOI
GND digital out / in
DI1
Activation of brake chopper - for discharging after mains
disconnection only
(external 24 V supply required)
DO1
Mains OK
DO2
Brake chopper active
DO3
Short circuit in brake chopper
DO4
Heatsink overtemperature
Conductor cross-section
2
[mm
]
0.2 ... 2.5
Tightening torque
[AWG]
[Nm]
24 ... 12
Spring terminal
Tightening torque
[AWG]
[Nm]
24 ... 12
Spring terminal
[lb-in]
[lb-in]