Diagnostics frame
In accordance with the PROFIBUS
[Get_Sl_Diag] service. The diagnostics data comprise standard diagnostics information (6
bytes according to the PROFIBUS
data. A maximum of 63 bytes can be inserted for the device-specific diagnostics data. Of
which the first 4 bytes are specified in the PROFIBUS
remain free for use (user_data).
The device related information is structured as follows:
sign_le
status_
n
type
Fig. 7: The device related information is structured as follows:
I
Encode the byte sign_len as fol‐
lows:
I.I
Length of the status DU including the
header byte: 04..63
[device related diagnostics] :
I.II
Flags
00b constant
II
Encode the byte status_type as
follows:
II.I
Status-Type: 48 (manufacturer spe‐
cific)
standard, the DMT provides you with the
®
®
standard) and possibly device-specific diagnostics
slot_nu
speci-
mber
fier
®
standard. Thereafter 59 bytes
user_da
ta 1
[Status] : 1
II.II
Flags
III
Encode the byte slot_number as
follows: Slot number (
[0] is used)
slot
IV
Encode the byte specifier as
follows:
IV.I
Status specification: 00
IV.II
Reserved
Functions
...
user_da
ta n
constant
b
[0] as only
constant
b
A0891
51