SubDrive Troubleshooting - Addendum
Condition
Indicator Lights
PRESSURE
FLUCTUATIONS
MOTOR FREQUENCY
(POOR
ON DISPLAY
REGULATION)
SYSTEM
REGULATES
DISPLAY SHOWS
BUT DISPLAY
SHOWS 199P
- Pressure sensor placement and setting
- Pressure gauge placement
GREEN
- Pressure tank size and pre-charge
- Air entrainment into pump intake
(lack of submergence)
- System Response setting
GREEN
The pressure in the system is
199P
SubDrive Connect Surface Pump
Possible Cause
- Leak in system
199psi or higher.
Corrective Action
- Correct pressure and
placement as necessary
- Tank may be too small for
system flow
- This is not a drive problem
- Disconnect power and check
pressure gauge for pressure drop
- Set deeper in the well or tank;
install a flow sleeve with airtight
seal around drop pipe and cable
- If fluctuation is only on branches
before sensor, enable Steady Flow
- Change tank size configuration
- Reduce frequency output range
- Reduce System Response
then reduce P and I value
The max pressure the display can
show is 199psi. Use the pressure
gauge or Wi-Fi / FE-Connect app
to view the system pressure.