Inlet Air Requirements

WARNING
Combustion Hazard
■ Provide a properly located and sized fresh air
inlet for the heater.
-- Refer to Inlet Air Requirements instructions.
■ Failure to provide a fresh air inlet can lead to:
-- Sooting causing building damage
-- High carbon monoxide levels, causing serious
injury or death to livestock and humans.
-- Overheating of the fi rst 10 ft. tube, causing
fi res leading to building damage and injury to
livestock and humans.
-- Higher temperature differences over the length
of the tubes, causing problems in temperature
control and bird performance
This heater requires clean, fresh air from a normal,
atmospheric pressure environment for proper opera-
tion and combustion. Contact L.B.White Company if
you have any questions regarding the installation of
this heater.
Inlet air may be drawn from the attic or through side
walls under a protective eve. See Figs. 3 and 4.
FIG. 3
Vent Cap
Air inlet
tube
A. Slide fl ange down
air inlet tube until
it meets bevel in
tube.
B. Attach fl ange to
tube using three
self drilling screws.
C. Firmly push vent
cap with screen
into tube.
-- All inlet air seams and joints must be sealed
-- Do not use any fi lters on the air inlet system
-- The air inlet system must be kept as
straight as possible. No more than 1 -
90º bend is allowed.
-- Contact L.B.White Co. if you have any questions
regarding the installation of the heater.
Inlet air for combustion MUST NOT be drawn
from:
■ Inside the confi nement room.
■ An attic or location where negative pressure
DRAWING INLET AIR FROM ATTIC
Ceiling
fl ange
12 in. from
Ensure inlet cap is
inside of
unblocked by insulation.
roof
Clamps
Owner's Manual • Sentry
Sentry Tube Heaters
(vacuum) affects the air draw of the heater's fan.
Examples include, but are not limited to:
a. Houses with attic soffi t vent area smaller than
ridge cap vent area
b. Heater air inlet located within 20 ft. of building
ventilation fans
c. Locations where wind and/or the elements can
create a negative pressure.
Inlet tube must be
12 in. min.
above insulation
Cut 4-1/4 in. hole in ceiling adjacent to
joist. Spread insulation away and fasten
ceiling fl ange to joist.
Flex tube: Cut to length
-- Do not exceed 4 ft. max. length
-- Do not kink (part #573382)
9