Do not exceed the rated output of the generator.
Figure 3 - Control Panel
14
15
16
17
2.1 PRE-USE CHECK AND SET-UP
Prior to starting the generator and adding loads, perform the following
tasks:
1. Make sure the generator in on a firm, level, non-combustible surface
with at least five (5) feet of clearance on all sides.
Never operate in an enclosed area or indoors!
NEVER use in the home, or in partly enclosed
areas such as garages, even if doors and
windows are open! ONLY use outdoors and far
from open windows, doors, vents, and in an
area that will not accumulate deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which can you cannot see or smell.
This poisonous gas, if breathed in sufficient
concentrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or
permit even partial blockage of ventilation
provisions, as this can seriously affect safe
operation of the generator. The generator
MUST be operated outdoors.
NOTE:
18
19
Section 2 – Operation
Portable Generator System
This exhaust system must be properly
maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
The manufacturer recommends installing a
battery operated carbon monoxide alarm
indoors, according to the manufacturers
instructions.
NEVER use in the home, or in partly enclosed areas
such as garages, campers or trailers. ONLY use
outdoors and far from open windows, doors, vents.
2. Remove the fuel cap and check the fuel level. If fuel is needed, see
the section "FUELING THE GENERATOR".
3. Remove the left side service cover and check the oil level by
removing the oil filler cap. The oil level should be to the bottom of the
threads on the oil fill pipe. If oil is needed, see the section "ADDING
ENGINE OIL".
4. Replace and secure the left side service cover.
5. Make sure there are no loads connected to the generator.
6. The National Electric Code (NEC) requires the frame and external
electrically conductive parts of the generator be properly connected
to an approved earth ground. Proper grounding of the generator will
prevent electrical shock in the event of a ground fault condition in the
generator or in connected electrical devices. Proper grounding also
helps dissipate static electricity, which often builds up in unguarded
devices.
7. Local electrical codes may also require proper grounding of the
generator.
Starting the generator with accessories connected
to the 120 VAC outlets will damage the generator
and the connected accessories.
5