Festo CPX−Terminal Instrucciones De Instalación página 21

Ocultar thumbs Ver también para CPX−Terminal:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 31
3. Screws must be placed so that the self−cutting threads
can be used. Tighten screws manually, crosswise.
Tightening torque 0.9 to 1.1 Nm.
3.3 Setting the DIL switch (not for CPX−4AE−TC)
Using the switching elements of the dual DIL switch,
set the following functions (see following table):
For modules 2AE−U−I, 4AE−I and 2AA−U−I:
the signal range
For temperature module 4AE−T:
the number of inputs.
DIL
2AE−U−I/2AA−U−I
switch 0
Signal range
Channel 0:
0 to 10 V
Channel 0:
0 to 20 mA
Channel 0:
4 to 20 mA
DIL
Appropriate for
switch 1
channel 1
Festo CPX−AX 0811c English
4AE−I
Signal range
Channel 0 + 1:
0 to 20 mA
Channel 0:
4 to 20 mA
Channel 1:
0 to 20 mA
Channel 0:
0 to 20 mA
Channel 1:
4 to 20 mA
Channel 0 + 1:
4 to 20 mA
Appropriate for
channel 2 + 3
4AE−T
Number of
inputs
4 inputs
2 inputs
Reserved
21

Publicidad

Tabla de contenido
loading