4
Technical data
For all modules
General technical data CPX ter
minal
Protection class per EN 60529
Operating voltage supply
Rated voltage
Intrinsic current consumption
at 24 V (internal electronics),
if not otherwise specified
Input modules CPX−2AE−U−I and
CPX−4AE−I
Channels
Signal ranges
Line length
Resolution (analogue−digital
converter)
Module cycle time
Sensor selection specifications
Permissible input voltage or
input current
Input resistance
Permissible potential difference
Between input channels
Between inputs and FE
24
Data
See CPX system description
(P.BE−CPX−SYS...)
See technical data
of the assembled connection block
V
(electronics/sensors)
EL/SEN
DC 24 V ± 25%
Type 50 mA (no current consump
tion at outputs, if at hand)
Voltage inputs
(only
CPX−2AE−U−I)
2
0 to 10 V
Max. 30 m, screened
12 Bit (internal),
scaleable to 15 Bit + prefix
2AE−U−I: 4 ms/4AE−I: 10 ms
30 V
100 k
AC 1 V
DC 30 V
Festo CPX−AX 0811c English
Current inputs
2AE−U−I:
2
4AE−I:
4
0 to 20 mA/
4 to 20 mA
40 mA
100
(type 50 )
AC 0 V
DC 30 V