9.5.2
Continuous purging function (only for
applications in which this is provided for)
Continuous purging is a function that maintains the air ventilation
independently of the request for burner ignition. From the mo-
ment when it is set, the motor remains in operation both when the
limit thermostat (TL) is not switched over (burner switched off),
and when the burner is in lockout.
Only when the limit thermostat (TL) is switched does the motor
stop for the standby time of four seconds (standby position = t2 +
t1).
The function can be set from the reset button when the limit ther-
mostat (TL) is not switched (burner off), by following the proce-
dure in the paragraph "Post-purging function (t6)", pressing the
button 7 times = continuous purging.
To reset this function, just press the button for 5 seconds until the
signalling LED turns to red, then release it without carrying out any
operation. Wait at least 20 seconds before restarting the burner.
If when the limit thermostat (TL) switches, there is an extraneous
light the motor stops as long as the extraneous light is there fol-
lowed by the block.
The control box leaves the factory with the following setting:
0 blinks = no continuous purging.
9.5.4
Function setting procedure using the reset button
Control box function
Reset
Visual diagnostic of the lockout
causes
Post-purging
Continuous purging
(only for suitable applications)
Long pre-purging
Reset of set functions
Reset of operational parameters
20015403
Maintenance
Actions on the reset button
1 - 2 seconds
3 seconds
5 seconds then press
once = 1 minute
5 seconds then press
7 times = continuous purging
5 seconds then press
8 times = long pre-purging
5 seconds
5 seconds
28
GB
9.5.3
Long pre-purging function (t7)
The long pre-purging makes it possible too lengthen the purging
of the air by the switching of the limit thermostat (TL) on the igni-
tion of the flame for up to two minutes.
The function can be set from the reset button when the limit ther-
mostat (TL) is not switched (burner off), by following the proce-
dure in the paragraph "Post-purging function (t6)", pressing the
button 8 times = long pre-purging.
To reset this function, just press the button for 5 seconds until the
signalling LED turns to red, then release it without carrying out
any operation. Wait at least 20 seconds before restarting the
burner.
The control box leaves the factory with the following setting:
0 blinks = no long pre-purging.
Status of possible use of the reset button
After lockout of control box
After lockout of control box
With limit thermostat (TL) not switched
(burner off)
With limit thermostat (TL) not switched
(burner off)
With limit thermostat (TL) not switched
(burner off)
With limit thermostat (TL) not switched
(burner off)
With limit thermostat (TL) switched over during pre-
purging