GATES WITH SINGLE LEAF
Installation of limit switch
• Connect the open limit switch to terminals
12 (FCA1) and 16 (COM)
• Connect the close limit switch to terminals
13 (FCC1) and 16 (COM)
Installation of encoder
• Connect the negative feeds (BLACK cable)
to terminal 16 (COM)
• Connect the positive feeds (RED cable)
to terminal 17 (24VAC)
• Connect the encoder output (BLUE / WHITE) to terminals
14 (FCA2) and 15 (FCC2)
OPERATIONAL TEST
To check whether the connections are correct after installation,
start the self-learning cycle (APPr menu)
• If during the self-learning cycle errors are not displayed the
encoders are connected correctly.
• If the display shows Err7 when door 1 begins to move,
swap the cables (BLUE / WHITE) connected to terminals
14 (FCA2) and 15 (FCC2)
• If the display shows Err7 when door 2 begins to move,
swap the cables (BLUE / WHITE) connected to terminals
12 (FCA1) and 13 (FCC1)

STOP

For a better safety, you can fit a stop switch that will cause the
immediate gate stop when activated. This switch must have a
normally close contact that will get open in case of operation.
In case the stop switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a start command (if the start function
in pause is disabled, it will be temporarily enabled to allow the
gate release).
Connect the stop switch cables between terminal 5 and 6 of the
control unit.
The stop switch function can be activated by means of a
remote control stored on channel 3 (see relevant instructions of
MR1 receiver). The command STOP from remote is operative also
if the input STOP of the terminal board is disabled.

ACTIVATION INPUTS

CITY1-ECD is equipped with two activation inputs, whose
operation depends on the programmed operation modes (see
Strt item of programming menu):
• Standard mode: a command being on the first input will
cause the complete opening of both leaves (start); a
command being on the second input will cause the partial
opening of leaf 1 only (pedestrian start).
• Open/Close command and manned operation:
a command on the first input always controls the gate
opening, while a command on the second input always
controls the gate closing.
In Open/Close mode, there is an impulse command, that is
to say that an impulse will cause the complete gate opening
or closing.
In manned operation, there is a monostable command, that
is to say, the gate will be opened or closed as long as the
contact is closed and it will immediately stop as the contact
is open.
• Timer mode: it is similar to the standard mode but the gate
stays open (completely or partially) while the contact is
closed on input; as soon as the contact is open the pause
time count down will start, after which the gate will be
closed again. This function allows programming the gate
opening time during the day, by making use of an external
timer. Automatic closing must be enabled.
In all modes, inputs must be connected to devices having
normally open contacts.
Connect cables of device controlling the first input between
terminals 3 and 6 of the control unit.
Connect cables of device controlling the second input between
terminals 4 and 6 of the control unit.
The first input function can also be activated by pressing UP key
outside the programming menu or by means of a remote control
stored on channel 1 (see relevant instructions of MR1 receiver).
The second input function can also be activated by pressing
DOWN key outside the programming menu or by means of a
remote control stored on channel 2.

EXTERNAL AERIAL

We suggest to use the external aerial (model ANSGP433) in order
to guarantee the maximal range.
Connect the antenna hot pole to terminal 1 of the control unit
and the braiding to terminal 2.
31