Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase.
StoP
The gate stops and its cycle is considered as finished.
APEr
The gate opens again.
Select option StoP, to set up the "step-by-step" operation logic.
Select option APEr, to set up the 'always open' operation logic.
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase.
ChiU
the gate starts closing.
no
command is ignored.
Select option ChiU, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Apart from selected option, the start command lets the gate close if it
has been stopped by a stop command or if the automatic closing was
not enabled.
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
PAUS
The gate stops and goes to pause.
ChiU
the gate immediately starts closing.
no
the gate goes on with the opening phase (command is ignored).
WARNING: a Start command in any phase of partial opening
will cause the total opening; the Start Pedestrian command is
always ignored during a total opening.
Automatic closing
During the automatic operation, the control unit will automatically close
the gate when a set-up time expires.
The Start command, if enabled by St.PA menu, allows closing the gate
before the set up time expires.
In semi-automatic operation, that is to say, if the automatic closing
function is disabled by setting the value to zero ('no' will be displayed),
the gate can be closed through the start command only: in this case,
St.PA menu setup will be ignored.
If the control unit receives a Stop command when the gate is in pause,
it will automatically pass to the semi-automatic operation.
Closing after transit
During the automatic operation, the pause count down starts from the
set up value each time a photocell operates during the pause.
If the photocell operates during the opening time, this time will be
immediately stored as pause time.
This function allows having a fast closing as soon as transit through the
gate is completed, therefore, a time shorter than Ch.AU is
generally used.
Ch.AU will be used when 'no' is set up.
As for semi-automatic operation, this function is not active.
40