ΔPC (bar) - Pressure head according to the temperature
20
25
-40
12.7
14.7
-35
12.2
14.3
-30
11.7
13.8
-25
11.1
13.2
10.4
12.5
-20
-15
9.6
11.7
-10
8.7
10.8
-5
7.6
9.7
0
6.4
8.5
5
5.1
7.2
10
5.7
15
Table 1: determine the design pressure head ΔP from the saturated evaporating temperature Tevap and condensing temperature Tcond for the chosen refrigerant.
Tliq [°C]
-22
-16
-10
CF
0.56
0.58
0.61
Table 2: identify the Correction Factor CF at the temperature nearest to Tliq (if no certain data is available, assume Tliq = Tcond – 5°C)
Tevap. 15°C
5
8
E2V09B
1.9
2.4
E2V11B
3.4
4.2
E2V14B
5.1
6.5
E2V18B
7.3
9.2
E2V24B
14.5
18.4
22.5
E2V35B
29.3
37
45.4
E4V55A
71
89.8
109.9
E4V65A
98
123
E4V85A
137
173
E4V95A
--
--
Tevap. 10°C
5
8
E2V09B
1.9
2.4
E2V11B
3.3
4.2
E2V14B
5.1
6.5
E2V18B
7.3
9.2
E2V24B
14.4
18.3
22.4
E2V35B
29.1
36.8
45.1
E4V55A
70.5
89
E4V65A
97
123
E4V85A
136
172
E4V95A
--
--
Tevap. 5°C
8
12
E2V09B
2.4
2.9
E2V11B
4.2
5.1
E2V14B
6.4
7.8
E2V18B
9.1
11.2
12.9
E2V24B
18.1
22.2
25.6
E2V35B
36.5
44.7
E4V55A
88.5
108.4
125.2
E4V65A
122
149
E4V85A
171
209
E4V95A
--
--
Tevap. 0°C
8
12
E2V09B
2.3
2.9
E2V11B
4.1
5.1
E2V14B
6.3
7.8
E2V18B
9
11
12.8
E2V24B
18
22
25.4
E2V35B
36.2
44.3
E4V55A
87.7
107
E4V65A
121
148
E4V85A
169
208
E4V95A
--
--
Table 3: The equivalent cooling capacity values in the table refer to a liquid temperature at the valve inlet = 38°C. For temperatures other than 38°C, in the table identify the
valve with the equivalent capacity RATING that is higher than or equal to the required rated cooling capacity CAP multiplied by the coeffi cient shown in Table 2. To allow for any
uncertainty in the design data, the values in the tables correspond to 80% of the maximum effective cooling capacity .
Tcond – Saturated condensing temperature (°C)
30
35
40
17.1
19.6
22.4
16.6
19.2
22
16.1
18.7
21.5
15.5
18.1
20.9
14.8
17.4
20.2
14
16.6
19.4
13.1
15.6
18.4
12.0
14.6
17.4
10.8
13.4
16.2
9.5
12
14.8
8
10.5
13.3
6.3
8.8
11.6
CF – Correction factor for the temperature (°C) of the liquid at the valve inlet
-4
2
8
0.64
0.67
0.71
RATING (kW) – Equivalent cooling capacity of the CAREL valves