ΔPC (bar) - Pressure head according to the temperature
20
25
-40
9.9
11.5
-35
9.5
11.1
-30
9.1
10.7
-25
8.6
10.3
-20
8.1
9.7
-15
7.5
9.1
-10
6.7
8.3
-5
5.9
7.5
0
5.0
6.6
5
5.5
10
4.4
15
Table 1: determine the design pressure head ΔP from the saturated evaporating temperature Tevap and condensing temperature Tcond for the chosen refrigerant.
Tliq [°C]
-22
-16
-10
CF
0.49
0.52
0.54
Table 2: identify the Correction Factor CF at the temperature nearest to Tliq (if no certain data is available, assume Tliq = Tcond –5°C)
Tevap. 15°C
4
6
E2V09B
1.2
1.4
E2V11B
2.1
2.5
E2V14B
3.1
3.8
E2V18B
4.5
5.5
E2V24B
8.9
10.9
E2V35B
17.9
21.9
E4V55A
--
--
E4V65A
--
--
E4V85A
--
--
E4V95A
--
--
Tevap. 10°C
4
6
E2V09B
1.1
1.4
E2V11B
2
2.5
E2V14B
3.1
3.8
E2V18B
4.4
5.4
E2V24B
8.7
10.7
E2V35B
17.6
21.5
E4V55A
--
--
E4V65A
--
--
E4V85A
--
--
E4V95A
--
--
Tevap. 5°C
4
6
E2V09B
1.1
1.4
E2V11B
2
2.4
E2V14B
3
3.7
E2V18B
4.3
5.3
E2V24B
8.5
10.5
E2V35B
17.2
21.1
E4V55A
--
--
E4V65A
--
--
E4V85A
--
--
E4V95A
--
--
Tevap. 0°C
6
8
E2V09B
1.3
1.5
E2V11B
2.4
2.7
E2V14B
3.6
4.2
E2V18B
5.1
5.9
E2V24B
10.2
11.8
E2V35B
20.6
23.8
E4V55A
--
--
E4V65A
--
--
E4V85A
--
--
E4V95A
--
--
Table 3: The equivalent cooling capacity values in the table refer to a liquid temperature at the valve inlet = 38°C. For temperatures other than 38°C, in the table identify the
valve with the equivalent capacity RATING that is higher than or equal to the required rated cooling capacity CAP multiplied by the coeffi cient shown in Table 2. To allow for any
uncertainty in the design data, the values in the tables correspond to 80% of the maximum effective cooling capacity .
Tcond – Saturated condensing temperature (°C)
30
35
40
13.2
15.2
17.3
12.9
14.8
17
12.5
14.4
16.6
12
14.0
16.1
11.5
13.4
15.6
10.8
12.8
14.9
10.1
12.1
14.2
9.3
11.2
13.4
8.4
10.3
12.4
7.3
9.3
11.4
6.1
8.1
10.2
4.8
6.8
8.9
CF – Correction factor for the temperature (°C) of the liquid at the valve inlet
-4
2
8
0.58
0.61
0.65
RATING (kW) – Equivalent cooling capacity of the CAREL valves