STEP 3.
Ensure Ignitor sparks only
!
against the hood of the pilot.
Ignitor should not spark against the flame sensor, brackets, heating
chamber, burner, etc. Adjust ignitor probe location if required.
- DO NOT twist ignitor wire or break from ceramic base.
- DO NOT use a broken ignitor.
STEP 4.
Determine that the pilot is igniting and burning properly and that
main burner ignition is satisfactory by turning the thermostat
off and back on. Make this determination with the appliance
burner both cold and hot. Perform this step as many times as is
necessary to satisfy yourself that the automatic intermittent pilot
system is operating properly.
- Sequence the appliance through at least three (3)
operating cycles.
- Check all furnace connections for gas leaks with leak
detector solution, including plug installed into valve body.
Do not use open flame.
STEP 5.
Re-install the heater door on the front of the
housing, at the base.
STARTING PILOT PRO SYSTEM PER ANSI Z21.71
Page 21
1018454-E