Instalación eléctrica
5
Normas de instalación
Short circuit current rating
Branch circuit protection
Motor overload protection
Ambient temperature
Wiring diagrams
82
Instrucciones de funcionamiento – MOVIGEAR
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected by 600 V non-semiconductor fuses or 500 V minimum
inverse time circuit breakers.
®
MOVIGEAR
, the max. voltage is limited to 500 V.
Suitable for motor group installation on a circuit capable of delivering not more than
5,000 rms symmetrical amperes when protected by maximum 40 A, 600 V non-semi-
conductor fuses or 500 V minimum 40 A maximum inverse time circuit breaker.
®
MOVIGEAR
, the max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
The table below list the permitted maximum branch circuit protection:
Series
®
MOVIGEAR
®
MOVIGEAR
is provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 150% of the rated motor current.
®
MOVIGEAR
is suitable for an ambient temperature of 40 °C, max. 55 °C with derated
output current. To determine the output current rating at temperatures above 40  °C,
the output current should be derated by 3.0% per K between 40 °C and 55 °C.
An additional speed-dependent derating may be required. For details, refer to chapter
"Technical data and dimension sheets".
For wiring diagrams, refer to chapter "Electrical installation".
®
-DBC-B
Non-semiconductor
fuses
40 A/600 V
Inverse time circuit
breakers
500 V minimum/
40 A maximum