INSTALLATION
The boiler must be installed in a fixed loca-
IT
tion and only by specialized and qualified
firms in compliance with all instructions
ES
contained in this manual.
Furthermore, the installation must be in
FR
accordance with current standards and
regulations.
BE
2. 1
BOILER ROOM
GB
"PLANET DEWY 60 BFR" boilers can be
installed in boiler rooms whose size and
RO
requirements meet current regulations.
Furthermore, vents, with surface areas at
RUS
least 3.000 sq. cm or 5.000 sq. cm for
Single installation with optional
kit (code 8101520)
M
C.H. flow
R
C.H. return
M2 Tank flow
R3 Tank return
Installation in sequence/cascade
R
C.H. return
M
C.H. flow
G
Gas connection
S3
Condensation outlet
104
gas with density over 0.8, must be installed
in the outer walls for room ventilation.
2.2
INSTALLATION
For single installations, it is also possible to
order an optional compensator kit (code
8101520).
The kit can be fitted on accumulation boilers
with a capacity equivalent to or above 80
liters.
For
installation
sequence/cascade operations, refer to the
example in fig. 3.
With control unit code 8096301, supplied
455
M2
265
M
S3
G
R
by Sime upon request, a maximum of four
boilers can be controlled. The control unit
kit is supplied with assembly and use
instructions.
2.3
To protect the heat system from damaging
corrosion, incrustation or deposits, after
installation it is extremely important to
clean the system using suitable products
for
single
or
such as, for example, Sentinel X300 or
X400. Complete instructions are provided
with the products but, for further informa-
tion, you may directly contact GE Betz.
WARNING:
R3
- In
146
500
sequence/cascade
tion, the heating system must
be equipped with a hydraulic
separator and safety compo-
nents.
- When replacing one or more
boilers in existing plants, it is
advisable to install a heat
exchanger to separate the boi-
ler circuit from the secondary
circuits. See the pressure
curve for the boiler supply
shown in figure 14.
M2
R
M
88
330
CONNECTING UP SYSTEM
both
single
and
installa-
Fig. 3