Table 8.2: Other Regions
Rated Current of
Nominal Cross-Sectional
Appliance (A)
≤ 6
6 - 10
10 - 16
16 - 25
25- 32
32 - 45
b. Using wire strippers, strip the rubber jacket
from both ends of signal cable to reveal
about 15cm (5.9") of the wires inside.
c. Strip the insulation from the ends of the
wires.
d. Using a wire crimper, crimp u-lugs on the
ends of the wires.
NOTE: While connecting the wires, please
strictly follow the wiring diagram (found inside
the electrical box cover).
2. Remove the electric cover of the outdoor unit.
If there is no cover on the outdoor unit,
disassemble the bolts from the maintenance
board and remove the protection board.
(See Fig. 8.1)
Fig. 8.1
3. Connect the u-lugs to the terminals
Match the wire colors/labels with the labels on
the terminal block, and rmly screw the u-lug
of each wire to its corresponding terminal.
4. Clamp down the cable with designated cable
clamp.
Area (mm²)
0.75
1
1.5
2.5
4
6
Cover
Screw
5. Insulate unused wires with electrical tape.
Keep them away from any electrical or metal
parts.
6. Reinstall the cover of the electric control box.
Harmonic declaration
"The equipment M4OB-36HFN8-Q complies
with IEC 61000-3-12 provided that the short-
circuit power Ssc is greater than or equal to
4787737.5 at the interface point between the
user's supply and the public system. It is the
responsibility of the installer or user of the
equipment to ensure, by consultation with the
distribution network operator if necessary, that
the equipment is con-nected only to a supply
with a short-circuit power Ssc greater than or
equal to 4787737.5."
"The equipment M5OD-42HFN8-Q complies
with IEC 61000-3-12 provided that the short-
circuit power Ssc is greater than or equal to
3190042.5 at the interface point between the
user's supply and the public system. It is the
responsibility of the installer or user of the
equipment to ensure, by consultation with
the distribution network operator if necessary,
that the equipment is con-nected only to a
supply with a short-circuit power Ssc greater
than or equal to 3190042.5."